description1
Zipper closure 1/5 zip athletic pullovers for men. Stretchy, lightweight, fast-drying fabric for superior performance. REGULAR FIT - US standard sizes. An athletic fit that sits close to the body for a wide range of motion, designed for optimal performance and all day comfort. FEATURES - Quarter zip closure;Thumbholes on long sleeves to keep them in place during workout
Specification
Name HIGH TEMPERATURE AIR SOURCE HEAT PUMP UNIT
Model HGYKT2-30CII
Power 3N~ 380V/50Hz
Performance Rated working condition High outlet working condition
Ambient Temperature DB/WB:40/35 ℃ DB/WB: 40/35 ℃
Inlet  Temperature 65 ℃ 80 ℃
Outlet  Temperature 75 ℃ 90 ℃
Heat Capacity 110W 95kW
Power Input 26.2W 32kW
COP 4.21 2.97
Hot Water Yield 9.4m³/h 8.1m³/h
Rated Current 47A
Maximum current 68A
Maximum power input 38kW
Noise ≤75db
Applicable Ambient Temperature -25~43 ℃
Product Dimension 1805*1035*2090 mm
Net weight 650 kg
Performance Curve

 

Heat Output of HGYKT2-30CII

Ambient Temperature℃

Heating Capacity
and Energy Efficiency

Water Outlet Temperature °C

45

50

55

60

65

70

75

80

85

90

10

Supplemental Air Unit
Heating Capacity(kW)

49.2

49.2

49.5

49.8

50.4

51.3

52.5

54.3

56.4

59.1

COP

3.83

3.61

3.4

3.18

2.95

2.73

2.52

2.31

2.13

1.96

15

Supplemental Air Unit
Heating Capacity(kW)

57

56.7

57

57

57.6

58.2

59.4

60.6

62.4

64.8

COP

4.22

3.96

3.72

3.47

3.23

2.99

2.75

2.53

2.33

2.14

20

Supplemental Air Unit
Heating Capacity(kW)

65.4

65.4

65.1

65.4

65.7

66

66.9

68.1

69.6

71.4

COP

4.66

4.35

4.07

3.79

3.52

3.26

3

2.76

2.53

2.33

25

Supplemental Air Unit
Heating Capacity(kW)

75

74.7

74.4

74.4

74.4

74.7

75.3

76.2

77.4

78.9

COP

5.17

4.8

4.46

4.14

3.93

3.54

3.26

3

2.75

2.52

30

Supplemental Air Unit
Heating Capacity(kW)

85.5

84.9

84.6

84.3

84.3

84.3

84.6

85.2

86.1

87.3

COP

5.78

5.3

4.89

4.51

4.17

3.84

3.54

3.25

2.98

2.73

35

Supplemental Air Unit
Heating Capacity(kW)

96.9

96.3

95.7

95.4

94.8

94.8

94.8

94.8

95.4

96.3

COP

6.51

5.89

5.38

4.93

4.53

4.17

3.82

3.51

3.21

2.94

40

Supplemental Air Unit
Heating Capacity(kW)

109.8

108.9

108.3

107.4

106.8

106.2

105.9

105.6

105.9

106.5

COP

7.4

6.59

5.95

5.41

4.94

4.51

4.13

3.78

3.45

3.15

45

Supplemental Air Unit
Heating Capacity(kW)

 

123

121.8

120.6

119.7

118.8

117.9

117.6

117.3

117.3

COP

 

7.44

6.62

5.95

5.38

4.89

4.46

4.06

3.7

3.38