description1
Zipper closure 1/5 zip athletic pullovers for men. Stretchy, lightweight, fast-drying fabric for superior performance. REGULAR FIT - US standard sizes. An athletic fit that sits close to the body for a wide range of motion, designed for optimal performance and all day comfort. FEATURES - Quarter zip closure;Thumbholes on long sleeves to keep them in place during workout
Specification
Name CO₂ Air Sourcec Heat pump
Model HCYK-40CII
Power 3N~ 380V/50Hz
Heating Mode Once heating
Performance Nominal working condition Standard working condition
Ambient Temperature DB/WB: 7/6 ℃ DB/WB: 25/20 ℃
Inlet  Temperature 30  ℃ 9  ℃
Outlet  Temperature 80  ℃ 55  ℃
Heat Capacity 87300W 140000W
Power Input 37400W 38000W
COP 2.34 3.68
Hot Water Yield 1.55m³/h 2.2m³/h
Rated Current 67A
Maximum starting current 155A
Maximum power input 39000W
Refrigerant R744
Charge 20 kg
Noise ≤ 68db
Applicable Ambient Temperature -25~43 ℃
Sheet metal material Hot-dip galvanized cold rolled plate
Product Dimension 2300*2201*2308 mm
Net weight 1400 kg
Performance Curve

 

HCYK-40CII Heating Capacity and COP per Unit of Horsepower for Each Water Outlet Temperature under Various Ambient (or Water Source) Temperatures (Return Water Temperature: 30°C)

Ambient Temperature
(or Water Source Temperature) °C

Heating Capacity
and Energy Efficiency

Water Outlet Temperature °C

45

50

55

60

65

70

75

80

85

90

-30

Air Source Unit Heating Capacity (kW)

48.4

50.8

52

52.8

53.2

53.2

53.6

54

 

 

COP

1.75

1.71

1.7

1.7

1.69

1.67

1.65

1.64

 

 

-20

Air Source Unit Heating Capacity (kW)

56

59.2

60.4

60.8

60.8

61.6

62

62.4

 

 

COP

2.03

1.98

1.97

1.97

1.96

1.96

1.94

1.92

 

 

-10

Air Source Unit Heating Capacity (kW)

62.8

65.2

66.4

67.2

68

68.4

69.2

69.6

70.4

70.8

COP

2.21

2.2

2.2

2.19

2.19

2.18

2.17

2.16

2.1

2.02

0

Air Source Unit Heating Capacity (kW)

82

86.4

87.6

89.6

90.4

91.2

92.4

93.2

94.4

95.2

COP

2.73

2.71

2.7

2.69

2.69

2.68

2.64

2.61

2.56

2.52

10

Air Source Unit Heating Capacity (kW)

103.6

109.6

112

114.4

116

117.2

118.8

120.4

122

123.2

COP

3.45

3.42

3.41

3.38

3.33

3.3

3.25

3.19

3.11

3.04

20

Air Source Unit Heating Capacity (kW)

125.2

134

137.2

140.8

142.8

144.8

147.2

148.8

151.2

153.2

COP

4.42

4.4

4.34

4.25

4.16

4.09

3.98

3.93

3.8

3.69

30

Air Source Unit Heating Capacity (kW)

142

152

156.4

160.8

163.6

166.4

169.2

171.2

174.4

176.8

COP

5.58

5.44

5.29

5.15

5.02

4.92

4.77

4.65

4.46

4.32

35

Air Source Unit Heating Capacity (kW)

152.4

160.8

164

170

172.4

174.8

178

180.4

183.6

186

COP

6.05

5.83

5.68

5.47

5.32

5.21

5.09

4.98

4.8

4.68