description1
Zipper closure 1/5 zip athletic pullovers for men. Stretchy, lightweight, fast-drying fabric for superior performance. REGULAR FIT - US standard sizes. An athletic fit that sits close to the body for a wide range of motion, designed for optimal performance and all day comfort. FEATURES - Quarter zip closure;Thumbholes on long sleeves to keep them in place during workout
Specification
Name CO₂ Air Sourcec Heat pump
Model HCYK-20CII
Power 3N~ 380V/50Hz
Heating Mode Once heating
Performance Nominal working condition Standard working condition
Ambient Temperature DB/WB: 7/6 ℃ DB/WB: 20/15 ℃
Inlet  Temperature 30  ℃ 15  ℃
Outlet  Temperature 80  ℃ 60  ℃
Heat Capacity 49872W 69606W
Power Input 19285W 16012W
COP 2.5 4.4
Hot Water Yield 0.86m³/h 1.33m³/h
Rated Current 32.9A
Maximum starting current 92A
Maximum power input 19500W
Refrigerant R744
Charge 14 kg
Noise ≤ 63db
Applicable Ambient Temperature -25~43 ℃
Sheet metal material Hot-dip galvanized cold rolled plate
Product Dimension 2300*1100*2308 mm
Net weight 810 kg
Performance Curve

 

 

HCYK-20CII Heating Capacity and COP per Unit of Horsepower for Each Water Outlet Temperature under Various Ambient (or Water Source) Temperatures (Return Water Temperature: 30°C)

Ambient Temperature
(or Water Source Temperature) °C

Heating Capacity
and Energy Efficiency

Water Outlet Temperature °C

45

50

55

60

65

70

75

80

85

90

-30

Air Source Unit Heating Capacity (kW)

24.2

25.4

26

26.4

26.6

26.6

26.8

27

 

 

COP

1.75

1.71

1.7

1.7

1.69

1.67

1.65

1.64

 

 

-20

Air Source Unit Heating Capacity (kW)

28

29.6

30.2

30.4

30.4

30.8

31

31.2

 

 

COP

2.03

1.98

1.97

1.97

1.96

1.96

1.94

1.92

 

 

-10

Air Source Unit Heating Capacity (kW)

31.4

32.6

33.2

33.6

34

34.2

34.6

34.8

35.2

35.4

COP

2.21

2.2

2.2

2.19

2.19

2.18

2.17

2.16

2.1

2.02

0

Air Source Unit Heating Capacity (kW)

41

43.2

43.8

44.8

45.2

45.6

46.2

46.6

47.2

47.6

COP

2.73

2.71

2.7

2.69

2.69

2.68

2.64

2.61

2.56

2.52

10

Air Source Unit Heating Capacity (kW)

51.8

54.8

56

57.2

58

58.6

59.4

60.2

61

61.6

COP

3.45

3.42

3.41

3.38

3.33

3.3

3.25

3.19

3.11

3.04

20

Air Source Unit Heating Capacity (kW)

62.6

67

68.6

70.4

71.4

72.4

73.6

74.4

75.6

76.6

COP

4.42

4.4

4.34

4.25

4.16

4.09

3.98

3.93

3.8

3.69

30

Air Source Unit Heating Capacity (kW)

71

76

78.2

80.4

81.8

83.2

84.6

85.6

87.2

88.4

COP

5.58

5.44

5.29

5.15

5.02

4.92

4.77

4.65

4.46

4.32

35

Air Source Unit Heating Capacity (kW)

76.2

80.4

82

85

86.2

87.4

89

90.2

91.8

93

COP

6.05

5.83

5.68

5.47

5.32

5.21

5.09

4.98

4.8

4.68